name: OT / ICS / SCADA Security description: Operational Technology and industrial control system security — Purdue model segmentation, industrial protocol analysis (Modbus, DNP3, S7, EtherNet/IP), PLC/HMI exposure, IEC 62443 alignment, and MITRE ATT&CK for ICS, for authorized and safety-conscious assessments version: 3.0.0 author: Masriyan tags: [cybersecurity, ot-security, ics, scada, modbus, dnp3, plc, iec62443, attack-ics, purdue-model]
OT / ICS / SCADA Security
Purpose
Enable Claude to assess Operational Technology (OT) and Industrial Control System (ICS) environments — PLCs, RTUs, HMIs, SCADA servers, historians, and field devices — with safety as the first constraint. Claude reasons about the Purdue/ISA-95 model, analyzes industrial protocols passively, maps adversary behavior to MITRE ATT&CK for ICS, and aligns recommendations to IEC 62443 and the NIST SP 800-82 guidance.
SAFETY & AUTHORIZATION — READ FIRST: OT systems control physical processes; a crashed PLC can mean equipment damage, environmental release, or loss of life. Default to passive, non-intrusive methods. Never send active scans, writes, or protocol fuzzing to production OT without written authorization, asset-owner sign-off, and a tested rollback/safety plan — ideally on a test bench or during a maintenance window. Confirm scope and the "do-no-harm" boundary before proceeding.
Activation Triggers
This skill activates when the user asks about:
- ICS / SCADA / OT / DCS security or industrial network assessment
- Modbus, DNP3, S7comm, EtherNet/IP, BACnet, OPC-UA, IEC 61850/104 protocols
- PLC, RTU, HMI, historian, or engineering-workstation security
- Purdue model / ISA-95 segmentation and IT/OT boundary review
- IEC 62443, NIST SP 800-82, or NERC CIP alignment
- MITRE ATT&CK for ICS technique mapping
- Internet-exposed ICS devices (Shodan/Censys dorks) or ICS asset inventory
- OT threat detection, anomaly monitoring, or ICS incident response
Prerequisites
pip install requests pyyaml
# Protocol libraries (lab use): pip install pymodbus scapy
Optional enhanced capabilities:
- Wireshark /
tsharkwith ICS dissectors (Modbus, DNP3, S7, ENIP, GOOSE) nmapICS NSE scripts (use read-only scripts only, with care)- GRASSMARLIN / passive asset-discovery tooling
- Shodan/Censys access for exposure checks (passive, external)
Core Capabilities
1. Architecture & Purdue Model Review
When asked to review OT architecture, map assets to Purdue levels and assess the boundaries:
| Level | Zone | Assets | Key control |
|---|---|---|---|
| 4–5 | Enterprise / IT | ERP, business network, internet | Should never directly reach L0–L2 |
| 3.5 | IDMZ | Jump hosts, patch/AV relays, historian replica | Brokered, inspected IT↔OT traffic only |
| 3 | Operations | SCADA servers, historians, engineering WS | Hardened, monitored |
| 2 | Supervisory | HMIs, control servers | |
| 1 | Control | PLCs, RTUs, IEDs | |
| 0 | Process | Sensors, actuators, drives |
Flag: missing IDMZ, flat IT/OT networks, dual-homed engineering workstations, remote vendor access bypassing the DMZ, and any direct path from L4/L5 to L0–L2.
2. Industrial Protocol Analysis (Passive-First)
Prefer reading a SPAN/TAP capture over active probing. From a PCAP, identify:
- Modbus/TCP (502) — function codes; flag writes (FC 5/6/15/16), unauthenticated reads, exposure beyond the cell.
- DNP3 (20000) — operate/direct-operate, lack of Secure Authentication (SAv5).
- S7comm / S7comm-plus (102) — PLC start/stop, program upload/download.
- EtherNet/IP + CIP (44818/2222) — forward-open, attribute writes.
- OPC-UA (4840) — security policy
None, anonymous sessions. - IEC 61850 GOOSE/MMS, IEC 60870-5-104 (2404), BACnet (47808) as present.
Note that most ICS protocols have no authentication or encryption by design — any reachable client can issue commands. Use scripts/ics_protocol_analyzer.py to summarize an exported PCAP and flag write/control operations and unexpected talkers.
3. Exposure & Asset Discovery
- Passive inventory from captures (MAC/OUI → vendor, protocol → device role).
- External exposure (read-only, external) via Shodan/Censys dorks — never expose live device details publicly:
port:502 product:Modbus,port:20000 source address,tag:ics,"Siemens, SIMATIC",port:47808,"Schneider Electric".
- For any device that must be reachable, document why, the compensating controls, and whether it should be behind the IDMZ instead.
- Active scanning, if authorized: use only read-only
nmapNSE (modbus-discover,s7-info,bacnet-info,enip-info) with low rate, never against safety-instrumented systems (SIS).
4. Threat Modeling — MITRE ATT&CK for ICS
Map plausible adversary paths using the ICS matrix tactics: Initial Access → Execution → Persistence → Evasion → Discovery → Lateral Movement → Collection → Command-and-Control → Inhibit Response Function → Impair Process Control → Impact. Reference high-signal techniques (e.g., T0883 Internet-Accessible Device, T0836 Modify Parameter, T0831 Manipulation of Control, T0814 Denial of Service, T0816 Device Restart/Shutdown). Anchor scenarios to real tradecraft (Stuxnet, TRITON/TRISIS targeting SIS, Industroyer/CRASHOVERRIDE, PIPEDREAM/INCONTROLLER).
5. IEC 62443 / NIST SP 800-82 Alignment
- Define zones and conduits; assign Security Levels (SL 1–4) per zone based on threat.
- Review against IEC 62443-3-3 system requirements (FR1 IAC, FR2 UC, FR3 system integrity, FR4 data confidentiality, FR5 restricted data flow, FR6 timely response, FR7 resource availability).
- Map to NIST SP 800-82r3 control overlays and NERC CIP where the asset owner is in scope (BES).
6. OT-Aware Detection & Incident Response
- Detection: baseline normal protocol talkers and command rates; alert on unexpected write/program-download, new en